User Guide DLX Series L00410623-1 81
Figure 8.2.5: Varistors on the DC side
8.2.9.2. AC Side
• No alarms are raised regarding the condition of the varistors on the AC side. Therefore,
they need to be checked regularly (at least once per year) or after lightning strikes.
• Replace the damaged varistor with DLX Varistor Kit ordered from Danfoss, part number
139B0570.
• The three varistors on the AC side are located in the right side of the connection area
above the AC terminal area.
• Note the orientation of the varistors if they need to be replaced.
Figure 8.2.6: Varistors on the AC side
Check Varistor
Measure the ohms between the terminal and the bent pin on each varistor as per the
below diagrams: