24 User Guide DLX Series L00410623-1
The PV strings may be ungrounded, or grounded through either the negative or the
positive string conductors.
The grounded DC conductors are connected to ground via the grounding strap.
The grounded conductors must be sized according to the local and national electrical
regulations, and only carry current when electrical malfunctions occur.
Follow the safety instructions and specifications from the different PV module
manufacturers regarding grounding requirements.
All metal parts of the DLX inverters are electrically bonded to ground through the
terminal labeled GND in the AC terminal block.
CAUTION
If the positive or negative PV conductors are grounded, then the grounding strap
must be connected to the DC ground terminal and the system must NOT be
grounded at any other point, as voltage potentials can appear and possibly
damage electrical components.
A minimum cross section area of 6.0 mm² / 10 AWG is required for the ground wire
connection.
4.3.4. DC Connections (PV)
The DC connections include wiring from the PV modules, possibly through a combiner
box, to the inverter. The inverter may be configured with the optional Stringbox.
DANGER
Always disconnect the PV array before starting the connection on the DC side!
Charged DC terminals pose a risk of serious injury or death as the PV array can
supply up to 600 V
DC
to the inverter when exposed to sunlight.
4.3.4.1. Array Configuration
A PV string consists of a certain number of PV modules connected in series. Strings can be
connected in parallel forming an array and attached to the inverter. The DLX inverters have
a large voltage range, and several feasible PV string configurations are possible. Follow the
module manufacturer instructions, and the local and national regulations when
configuring the PV array!
The grounding configuration of the PV array and the connection to the DC terminals
depend on the module technology used and the local or national electrical regulations.
The inverter is delivered from the factory in an ungrounded PV string configuration as
standard, but may be configured for positive or negative grounded PV strings.
The configuration of a negative grounded PV string differs from an ungrounded PV
string with the addition of a grounding strap.