User Guide DLX Series L00410623-1 43
CAUTION
The selected grid code must match the actual installation site; otherwise the
inverter may not operate or be compliant to relevant local and national
regulations due to incorrect limit values.
NOTICE
UK: Follow the local electrical regulations when selecting the grid code setting;
either normal grid code setting or UK 16A Limit restricted grid code setting with a
16A limitation for G83 compliance.
Germany: Follow the local electrical regulations when selecting the grid code
setting; either Germany 126 (VDE 0126-1-1) or Germany 4105 (VDE-AR-N 4105).
The following screen is displayed while inverter settings are being updated:
Grid Code Selection
NOTICE
An installation timer ensures that the grid settings can be changed (using the
Owner password) within 5 hours of feeding power to the grid. Thereafter it is only
accessible using the Installer password, which may only be obtained for installers
and grid operators by contacting Danfoss.
This step shows the configured Reactive Power Setting. If the setting is incorrect, press
Enter to call up the options and select the correct standard.