14 User Guide DLX Series L00410623-1
3.2. Site Preparations
Observe the following precautions when mounting and installing the DLX inverter on a
suitable site. This is crucial to maintaining the efficiency of the inverter!
3.2.1. Mounting
Sufficient ventilation and appropriate ambient temperatures are needed to prevent
temperature build-up inside the inverter, which could lead to possible power losses.
CAUTION
Insufficient cooling may lead to degradation of performance! Ensure sufficient air
space around the inverter and unblocked ventilation openings for optimum
cooling and efficient operation.
Observe the minimum distances below to maintain optimal cooling.
Figure 3.2.1: Minimum distances for optimal cooling
1. 400 mm
2. 300 mm
3. 150 mm
4. 150 mm
WARNING
Correct installation prevents the inverter from falling from the wall. The mounting
surface must be suitable for the weight (20-22 kg) and temperature (90° C) of the
inverter.
• The inverter must be mounted in a vertical position.
• Keep the lower cover closed when mounting the inverter to avoid damage to internal
components.
• It is recommended that the inverters are not installed in living areas due to possible
noise levels of the inverters.
• For ease of inspection and maintenance of the inverter, the display should be at eye-
level, and the product label must be visible and the connection area readily accessible.