Extra protection with regard to indirect contact
ELCB relays, multiple protective grounding or
grounding can be used as extra protection, provided
that local safety regulations are complied with. In
the case of an ground fault, a DC content may
develop in the faulty current.
Never use ELCB relays, type A, since such relays
are not suitable for DC fault currents.
If ELCB relays are used, this must be:
Suitable for protecting equipment with a direct
current content (DC) in the faulty current
(3-phase bridge rectifier)
Suitable for power-up with short charging
current to ground
Suitable for a high leakage current
MG.80.A6.22 - VLT is a registered Danfoss trademark