VL 8000 AQUA
Installation
Mechanical installation
Please pay attention to the requirements
that apply to integration and field mounting
kit, see the below list. The information given
in the list must be observed to avoid serious damage
or injury, especially when installing large units.
The adjustable frequency drive must be
installed vertically.
The adjustable frequency drive is cooled by means
of air circulation. For the unit to be able to release its
cooling air, the minimum distance over and below the
unit must be as shown in the illustration below.
To protect the unit from overheating, it must be ensured
that the ambient temperature does not rise above the
max. temperature stated for the adjustable frequency
drive and that the 24-hour average temperature is not
exceeded. The max. temperature and 24-hour average
can be seen from the General Technical section.
When installing the adjustable frequency drive on
a non flat surface, i.e. a frame, please consult
the instruction, MN.50.XX.YY.
If the ambient temperature is in the range of 45° C
- 55° C, derating of the adjustable frequency drive
will be required in accordance with the diagram in
the Design Guide. The service life of the adjustable
frequency drive will be reduced if no allowance is made
for the derating for ambient temperature.
Installation of VLT 8006-8352
All AFDs must be installed in a way that
ensures proper cooling.
Cooling
All units require a minimum space above and
below the enclosure.
MG.80.A6.22 - VLT is a registered Danfoss trademark
47
Vedere la pagina 0
1 2 3 4 5 6 ... 40 41

Sommario

Pagina 1 - VLT® 8000 AQUA

VLT® 8000 AQUAInstallation Mechanical installationPlease pay attention to the requirementsthat apply to integration and field mountingkit, see the be

Pagina 2

VLT® 8000 AQUA EMC-correct electrical installation525-600 V units do not comply with EuropeanEMC and Low Voltage Directives.The following is a guidel

Pagina 3

VLT® 8000 AQUAInstallationMG.80.A6.22 - VLT is a registered Danfoss trademark57

Pagina 4

VLT® 8000 AQUAMG.80.A6.22 - VLT is a registered Danfoss trademark58

Pagina 5

VLT® 8000 AQUAInstallation Earthing/Grounding of shielded/armoredcontrol cablesGenerally speaking, control cables must be shielded/armored and the sh

Pagina 6

VLT® 8000 AQUA Electrical installation, enclosuresCompact IP 54/NEMA 12VLT 8006-8011, 380-480 VCompact IP 20/NEMA 1VLT 8006-8011, 380-480 VVLT 8002-8

Pagina 7

VLT® 8000 AQUAInstallationCompact IP 54/NEMA 12VLT 8006-8032, 200-240 VVLT 8016-8072, 380-480 VCompact IP 20/NEMA 1VLT 8042-8062, 200-240 VVLT 8100-81

Pagina 8

VLT® 8000 AQUACompact IP 20/NEMA 1VLT 8102-8122, 380-480 VCompact IP 54/NEMA 12VLT 8102-8122, 380-480 VIP 00/ChassisVLT 8200-8300, 525-600 VCompact IP

Pagina 9

VLT® 8000 AQUAInstallationIP 54/NEMA 12, IP 21/NEMA 1VLT 8152-8352, 380-480 VIP 00/ChassisVLT 8152-8352, 380-480 VIP 54/NEMA 12, IP 21/NEMA 1 with dis

Pagina 10

VLT® 8000 AQUACompact IP 00/Chassis, IP 20/NEMA 1,and IP 54/NEMA 12VLT 8450-8600, 380-480 VMG.80.A6.22 - VLT is a registered Danfoss trademark64

Pagina 11

VLT® 8000 AQUAInstallation Electrical installation, power cablesIP 20/NEMA 1VLT 8006-8032, 200-240 VVLT 8016-8122, 380-480 VVLT 8016-8072, 525-600 VC

Pagina 12

VLT® 8000 AQUASide by side/flange by flangeAll AFDs can be mounted side by side/flange by flange.d[mm/in] CommentsCompact (all enclosure types)VLT 800

Pagina 13

VLT® 8000 AQUA Electrical installation, power cablesIP 00/Chassis and IP 20/NEMA 1VLT 8042-8062, 200-240 VVLT 8100-8150, 525-600 VIP 00/Chassis and I

Pagina 14

VLT® 8000 AQUAInstallation Electrical installation, power cablesCompact IP 00/Chassis, IP 20/NEMA 1, and IP 54/NEMA 12VLT 8450-8600 380-480 V without

Pagina 15

VLT® 8000 AQUA Use of EMC-correct cablesBraided shielded/armored cables are recommendedto optimise EMC immunity of the control cables andthe EMC emis

Pagina 16

VLT® 8000 AQUAInstallation Tightening torque and screw sizesThe table shows the torque required when fittingterminals to the AFD. For VLT 8006-8032,

Pagina 17

VLT® 8000 AQUA Line connectionLine must be connected to terminals 91, 92, 93.Nos. 91, 92, 93 Line voltage 3 x 200-240 VL1, L2, L3 Line voltage 3 x 38

Pagina 18

VLT® 8000 AQUAInstallationThe total current consumption of the motorsis not to exceed the maximum rated outputcurrent IVLT,Nfor the AFD.Problems may a

Pagina 19

VLT® 8000 AQUA Motor thermal protectionThe electronic thermal relay in UL-approved AFD hasreceived UL-approval for single motor protection, aslong as

Pagina 20

VLT® 8000 AQUAInstallation Control cardAll terminals for the control cables are locatedunder the protective cover of the AFD.The protective cover (se

Pagina 21

VLT® 8000 AQUA61 Termination of serial communication.See Earthing/Grounding of shielded(armoured control cables.This terminal is not normally to beuse

Pagina 22

VLT® 8000 AQUAInstallation Bus connectionThe serial bus connection in accordance with the RS485 (2-conductor) norm is connected to terminals68/69 of

Pagina 23

VLT® 8000 AQUAInstallation Installation of VLT 8450-8600 380-480 V Compact IP00/Chassis, IP 20/NEMA 1 and IP 54/NEMA 12Cooling Side-by-sideAll units

Pagina 24

VLT® 8000 AQUA Connection example VLT 8000 AQUAThe diagram below gives an example of a typicalVLT 8000 AQUA installation.The line supply is connected

Pagina 25

VLT® 8000 AQUAInstallation Connection examples Single-pole start/stop- Start/stop using terminal 18.Parameter 302 = Start [1]- Quick-stop using term

Pagina 26

VLT® 8000 AQUA 3-wire start/stop- Stop inverse by means of terminal 32.Parameter 306 = Stop inverse[14]- Latched start using terminal 18.Parameter 30

Pagina 27

VLT® 8000 AQUAInstallation Control unit LCPThe front of the AFD features a control panel - LCP(Local Control Panel). This is a complete interface for

Pagina 28

VLT® 8000 AQUA[QUICK MENU] gives access to theparameters used for the Quick menu.It is possible to switch between theQuick menu and the Extend menumod

Pagina 29

VLT® 8000 AQUAInstallationNOTEAn active HAND-OFF-AUTO signal via the digitalinputs will have higher priority than the controlkeys [HAND START]-[AUTO S

Pagina 30

VLT® 8000 AQUA Display mode II:This display mode makes it possible to have threeoperating data values displayed at the same timein line 1. The operat

Pagina 31

VLT® 8000 AQUAInstallation Navigation between display modes175ZA697.10HAND LOCAL RUNNING0 ---- 60Display mode I40.0HzAUTO REMOTE RUNN

Pagina 32

VLT® 8000 AQUA Changing dataRegardless of whether a parameter has beenselected under the Quick menu or the Extendedmenu, the procedure for changing d

Pagina 33

VLT® 8000 AQUAInstallation Infinitely variable change of numeric data valueIf the chosen parameter represents a numeric datavalue, a digit is first s

Pagina 34

VLT® 8000 AQUA General information about electrical installation High voltage warningThe voltage of the AFD is dangerouswhenever the equipment is co

Pagina 35

VLT® 8000 AQUA Quick MenuThe QUICK MENU key gives access to 12 of themost important setup parameters of the drive. Afterprogramming, the drive will,

Pagina 36

VLT® 8000 AQUAInstallationNOTEProgramming of extended parameters functionsavailable through EXTENDED MENU key isdone in accordance with same procedure

Pagina 37

VLT® 8000 AQUAInstallationor iron. Shield armor intended for mechanicalprotection, for example, is not suitable.MG.80.A6.22 - VLT is a registered Danf

Pagina 38

VLT® 8000 AQUA Extra protection with regard to indirect contactELCB relays, multiple protective grounding orgrounding can be used as extra protection

Pagina 39

VLT® 8000 AQUAInstallation RFI switchMains supply isolated from earth:If the adjustable frequency drive is supplied from anisolated mains source (IT

Pagina 40

VLT® 8000 AQUAVLT 8032 - 8042 525 - 600 VCompact IP 20/NEMA 1VLT 8052 - 8122 380 - 480 VVLT 8027 - 8032 200 - 240 VVLT 8052 - 8072 525 - 600 VCompact

Pagina 41

VLT® 8000 AQUAInstallation High voltage testA high voltage test can be carried out by short-circuitingterminalsU,V,W,L1,L2and L3and energizingby max.