3.1.1.Technical data
MODEL
HOTJET 8i
HOTJET 11i
HOTJET 15i
Performance data
Power output / Power input / COP
Power output / Power input / COP
Power output / Power input / COP
A7/W35
7,8 / 2,04 / 3,8
9.3 / 2.45 / 3.8
10.8 / 2.79 / 3.8
A2/W35
7,2 / 2,01 / 3,6
8.6 / 2.39 / 3.6
10.1 / 2.76 / 3.6
A7/W45
7,4 / 2,46 / 3,0
8.8 / 2.93 / 3.0
10.3 / 3.39 / 3.0
A2/W45
6,6 / 2,46 / 2,7
8.0 / 2.96 / 3.0
9.3 / 3.44 / 2.7
Technical data
Temperature operating limits for
air
-20 °C to 35 °C
-20 °C to 35 °C
-20 °C to 35 °C
Temperature limit of heating
system
+15 to +55°C (below outdoor temperature -10°C max. output temperature 50°C)
+15 to +55°C (below outdoor temperature -10°C max. output temperature 50°C)
+15 to +55°C (below outdoor temperature -10°C max. output temperature 50°C)
Heating and reversing water
communication pipe
3/4’’
3/4’’
3/4’’
Heating water flow rate
1.3 m³/h
1.5 m³/h
1.8 m³/h
Head loss, heating side
<20kPa
<20kPa
<20kPa
Protection against freezing
water heating
yes
yes
yes
Air flow rate
2 200 m³/h
2 200 m³/h
2 200 m³/h
Air channel diameter
400mm
400mm
400mm
Refrigerant circuit
Refrigerant
R407C
R404A
R407C
Refrigerant quantity ( Kg )
2.1
2.3
2.4
Defrosting
Automatic, according to the need. Upon request (manual)
Automatic, according to the need. Upon request (manual)
Automatic, according to the need. Upon request (manual)
Way of defrosting
By hot coolant (reversal)
By hot coolant (reversal)
By hot coolant (reversal)
Heating of the condensate bulk
tank
yes
yes
yes
Condensate drainage
By a hose
By a hose
By a hose
Cut-off pressure of low-
pressure pressurestat
0.08 MPa
0.08 MPa
0.08 MPa
Cut-off pressure of high-
pressure pressurestat
2.8 MPa
2.8 MPa
2.8 MPa
Technical information, weight
Dimensions (W x D x H)
1040 x 632 x 902 mm
1040 x 632 x 902 mm
1040 x 632 x 902 mm
Weight
210 kg
210 kg
215 kg
Placement
Designed for internal installation (there are holes on the walls for air suction and air
outlet)
Designed for internal installation (there are holes on the walls for air suction and air
outlet)
Designed for internal installation (there are holes on the walls for air suction and air
outlet)
Anti-corrosive protection
Powder coat,, galvanized sheet, cataphoresis
Powder coat,, galvanized sheet, cataphoresis
Powder coat,, galvanized sheet, cataphoresis
Color
RAL 7036
RAL 7036
RAL 7036
Degree of protection ( EN 60
529 )
Model i : IP40
Model i : IP40
Model i : IP40
Electrical connection
3/N/PE ~400 V, 50 Hz
3/N/PE ~400 V, 50 Hz
3/N/PE ~400 V, 50 Hz
Power supply - 3 phases
400V / 3 / 50Hz
400V / 3 / 50Hz
400V / 3 / 50Hz
Compressor
Copeland scroll
Copeland scroll
Copeland scroll
Service current [A]
4.5
5
5.8
Starting current [A]
18
20
23
Maximum service current [A]
6.5
7
8.8
Compressor protection [A]
16B
16B
16B
Compressor supply line (n x
mm2)
5x1.5
5x1.5
5x1.5
Hotjet CZ s.r.o.! ! 21 z 46
Operating instructions and installation of heat pumps Hotjet (3.08/2010/01)
!!