10.4.2. Managing Reactive Power Using TLX CN+
The TLX CN+ inverter provides controlled reactive power by using an external setpoint source,
i.e. a third-party product.
Note:
For TLX CN+ inverters:
Inverter control of reactive power is only possible for medium-voltage or custom grid codes.
Illustration 10.3: Example: Managing Reactive Power Using TLX CN+
1 DNO interface (radio receiver)
2 Third-party product
10.4.3. Managing Reactive Power Using TLX CN Pro+
The TLX CN Pro+ inverter is capable of controlling reactive power for an entire plant via the
master inverter functionality, configurable via the Web Server, at [Plant Setup Grid man-
agement].
The inverter allocated to act as master controls the reactive power settings of all other inverters
in the plant, transmitting settings for reactive power Q and power factor PF.
Illustration 10.4: Example: Managing Reactive Power Using TLX CN Pro+
1 DNO interface (radio receiver)
2 Danfoss Grid Management Box
Set the following parameters at [Plant Setup Grid management General]:
10. Ancillary Services
L00410582-01_02 89
10