Procedure for authorised technician:
1. Contact the service hotline to obtain a one-day level 2 password.
2. Access and change the grid code setting via the Web Server or the local display.
- To change settings via the Web Server, use remote access.
- The inverter logs the parameter change.
3. Complete and sign the form ‘Change of Functional Safety Parameters’.
- For local display access: Fill out the form by hand.
- For Web Server access:
Generate a settings report.
Fill out the form generated by the Web Server on the PC.
4. Send the following to the DNO:
- The form ‘Change of Functional Safety Parameters’, completed and signed.
- Letter requesting copy of authorisation to be sent to the PV plant owner.
4. Change of Functional Safety Settings