InstallationGuideECLComfort210/310,applicationA214/A314
5.11Application



ECAaddr.(choiceofRemoteControlUnit)A214.1/
A214.3/A214.5/A314.2/A314.3
11010
CircuitSettingrange
Factorysetting
1
OFF/A/BOFF
Decidestheroomtemperaturesignaltransferandcommunicationwiththe
RemoteControlUnit.
OFF:


A:

B:


SenddesiredT
11500
CircuitSettingrange
Factorysetting
1
OFF/ONON
Whenthecontrolleractsasaslavecontrollerinamaster/slavesystem,
informationaboutthedesiredowtemperaturecanbesenttothemaster
controllerviatheECL485bus.
OFF:


ON:






 


