not be able to reset (automatically or manually) a
dry run trip before the timer has expired.
472 Boost Time-Out
(BOOST TIMEOUT)
Value:
0 (DISABLE) - 999 s
30 min.
Function:
Use this parameter to specify the maximum time spent
to reach the Boost setpoint specified in parameter
406. If the boost setpoint cannot be reached within the
specified time, the frequency converter will continue
in normal operation (Not entering sleep mode).
Description of choice:
Set the maximum number of seconds allowed to
reach the value of Boost Setpoint, par. 406.
= factory setting. () = display text [] = value for use in communication via serial communication port