Wiring
Digital Inputs – Push Button
Normally Closed (NC) - Momentary (Push Button)
Multiple stop commands can be wired in series to
accommodate more stop commands. Any switch opens, stops
the motor.
If more stop commands are needed the diagram above shows multiple NC PB stop switches
using one Digital Input. If any of the 5 switches are opened the drive stops. With each input
programmed as a Stop Inverse command, the drive stays off until it sees a “Latched Start”
command.