3.1.4. Baud Rate Setting
All DeviceNet stations connected to the same bus network must have the same Baud rate. The
baud rate of the frequency converter can be selected via:
- Hardware switches
- Par. 10-01
Baudrate Select
(default 125k Baud)
- Object Class code 0x03, Instance 1, Attribute 2.
3.1.5. Setting the DeviceNet Baud Rate using the Hardware Switches
Using the hardware switches it is possible to
select a baud rate of 125k baud (factory set-
ting), 250k baud or 500 k baud according to
the following table:
Baud rate switch
8 7
Par. 10-01 1 1
125 k Baud 0 0
250 k Baud 0 1
500 k Baud 1 0
NB!
Switch off the power supply before changing the hardware switches.
The baud rate change will come into effect at the next power-up, and can be read in par. 10-01
Baudrate select
.
3.1.6. Setting the DeviceNet Baud Rate via Par. 10-01
Baudrate se-
lect
The baud rate can be set via par. 10-01
Baudrate select
if the hardware switches 1 and 2 are set
to ON (factory setting). The baud rate change will come into effect at the next power-up.
3.1.7. Setting the DeviceNet Baud Rate with the Object Class Code
0x03 Attribute 2
The baud rate can be set via the DeviceNet object class code 0x03 attribute 2 command, if the
hardware switches 1 and 2 are set to ON (factory setting). A new baud rate becomes effective
immediately after the class code 0x03 attribute 2 command.